AUTOMATIC TRANSFER SWITCH CONTROL MODULE
Model No: ATS105DMS
PREFACE
The configurable ATS controller model ATS105DMS allows for many of the demanding applications in the modern power supply network to be achieved.
The ATS105DMS is designed as an end of line transfer controller between two power supplies of typically similar security and availability.
It includes single phase sensing and timing functions to take account of PREFERRED SUPPLY FAILED delay and RETURN TO PREFERRED SUPPLY delay as well as the delay between control outputs to take consideration of contactor operating times.
Inputs are provided for the remote selection of the PREFERRED SUPPLY and RETURN INHIBIT.
HOW IT WORKS
Download PDF Manual From This Link:
https://drive.google.com/open?id=1-Pacuzn77iS6qEYTdCXIRxgry_PoNmmh
Under normal conditions with the default preferred supply as SUPPLY 1 and that supply is being available, the SUPPLY 1 output relay would be energized closing the SUPPLY 1 contactor 1 and connecting SUPPLY 1 to the load. When SUPPLY 1 becomes unavailable, the preferred supply failed delay timer is initiated and should it time out, the SUPPLY 1 output relay would be de-
energized opening the SUPPLY 1 contactor 1 and disconnecting SUPPLY 1 from the load. After the internal switching delay and considering SUPPLY 2 is available, the SUPPLY 2 output relay would be energized closing the SUPPLY 2 contactor 2 and connecting SUPPLY 2 to the load. On return of SUPPLY 1 to a healthy state the return to preferred supply delay timer is initiated and should it time out successfully without disturbance, the SUPPLY 2 output relay would be de-
energized opening the SUPPLY 2 contactor 2 and disconnecting SUPPLY 2 from the load. After the internal switching delay and considering SUPPLY 1 is within range, the SUPPLY 1 output relay would be energized closing the SUPPLY 1 contactor 1 and re-
connecting SUPPLY 1 to the load. If the return inhibit was applied whilst ALTERNATIVE SUPPLY is on load, on return of PREFERRED SUPPLY to a healthy state the controller would however remain on ALTERNATIVE SUPPLY until RI push button is pressed again making return inhibit function inactive.
Time delays are set via 5 pole DIP switch fitted on the back of the controller and selection possible as per TABLE “A” and “B”, typically the return to preferred supply delay is TWICE the preferred supply failed delay.
CONNOTATION
TERMINAL
Battery power supply (+)
1
Battery power supply (–)
2
Supply 1 relay output
13
Supply 1 relay input
14
Supply 2 relay output
15
Supply 2 relay input
16
Preferred supply external switch input
17
Return inhibit external switch input
18
Supply 2 AC power supply input (N)
19
Supply 2 AC power supply input (L)
20
Supply 2 AC power supply (LINK to 16)
21
Supply 1 AC power supply (LINK to 14)
22
Supply 1 AC power supply input (L)
23
Supply 1 AC power supply input (N)
24
ATS105DMS (BACK PLATE)
Download PDF Manual:
https://drive.google.com/open?id=1-Pacuzn77iS6qEYTdCXIRxgry_PoNmmh
Specifications
DC Supply: 12V or 24V (8...40Vdc)
Max. Operating Current: 80 mA at 12V
Max. Standby Current: 10 mA at 12 V
Supply 1/Supply 2 Input Range: 100 - 300 V AC
Frequencies supported: 50Hz and 60Hz
Supply 1/Supply 2 Contactor Relay output:12 Amp at 240V AC
Dimensions: 72 X 72 X 60mm
Operating Temperature Range: -30 to +70°C
*Important note: contactors (external relays) and other related items (fuses, cables, wires, interlocks etc) not included.
You are purchasing ATS105DMS control module only.
If a ready built panel is required please see "other items" in GenControl eBay shop (eBay item number: 322399958745)
We have a wide range of contactors (any size, 3 and 4 pole) available. Please send us your inquiry.
Under normal conditions with the default preferred supply as SUPPLY 1 and that supply is being available, the SUPPLY 1 output relay would be energized closing the SUPPLY 1 contactor 1 and connecting SUPPLY 1 to the load. When SUPPLY 1 becomes unavailable, the preferred supply failed delay timer is initiated and should it time out, the SUPPLY 1 output relay would be de- energized opening the SUPPLY 1 contactor 1 and disconnecting SUPPLY 1 from the load. After the internal switching delay and considering SUPPLY 2 is available, the SUPPLY 2 output relay would be energized closing the SUPPLY 2 contactor 2 and connecting SUPPLY 2 to the load. On return of SUPPLY 1 to a healthy state the return to preferred supply delay timer is initiated and should it time out successfully without disturbance,